• Model NO.: xlpe insulated power cable
  • Current: AC Cable
  • Sheath Material: PVC
  • Wire Core Material: Red Copper Wire
  • Trademark: Yifang
  • Specification: GB, IEC, BS, ASTM, etc.
  • HS Code: 8544464120
  • Voltage: Low and Medium Voltage Cable
  • Insulation Material: XLPE
  • Material Shape: Round Wire
  • Certification: ISO, CCC, CE, RoHS, UL, VDE
  • Transport Package: Wooden Drum, Wooden Iron Drum, Steel Drum, etc
  • Origin: China
Constructions 
 
Conductor: Compacted Stranded Copper conductor, Class 2 as per IEC 60228 
 
Conductor Screen: Semi-conductor (MV only)
 
Insulation: XLPE
 
Insulation Screen: Semi-conductor  (MV only)

 
Separate Screen: Copper Tape or Copper Wire & Tape
 
Wrapping Tape : Non-woven
 
Inner Covering:  Extruded PVC  (Armored only)
 
Armour : Steel Wire, or Steel Tape, or Aluminium Wire optional (Armored only)
 
Sheath: PVC/ST3 to IEC 60502, black, PE, Flame Retardant PVC, LSOH 
 
Note: Insulation color as per standards or customer requirement 
 

Applications
 
Used for power transmission and distribution line with voltage rated at 35kV and below.
Compared with PVC Insulated Power Cable, xlpe power cable boasts not only characteristics of excellent electricity, mechanism, heat and aging-resistant, environment stress-resistant and chemical corrosion-resistant, but also simple structure, light weight, no restriction by laying drop, and high temperature allowance for long-term working.
 
Standards
 
International: IEC 60502-2, IEC 60228
China: GB/T 12706.2-2008
Other standards such as BS,DIN and ICEA upon request
 Specifications
 
YJV Copper Conductor, XLPE Insulated, PVC Sheathed Power Cable For laying indoors and outdoors. Able to bear certain traction during installation, but not external mechanical forces. Laying single core cable in magnetic ducts is not allowed.
YJLV Al. Conductor, XLPE Insulated, PVC Sheathed Power Cable
YJY Copper Conductor, XLPE Insulated, PE Sheathed Power Cable For laying indoors and outdoors. Able to bear certain traction during installation, but not external mechanical forces. Laying single core cable in magnetic ducts is not allowed.
YJLY Al. Conductor, XLPE Insulated, PE Sheathed Power Cable
YJV22 XLPE Insulated,Steel Tape Armored,PVC Sheathed Power Cable Suitable for burying in ground, Able to bear external mechanical forces but large pulling forces.
YJLV22 Al. Insulated,Steel Tape Armored,PVC Sheathed Power Cable
YJV32 Copper Conductor, XLPE Insulated, Fine Steel Wire Armored,PVC Sheathed Power Cable Apply to shafts,water and soil,able to bear the larger positive pressure.
YJLV32 Al.Conductor, XLPE Insulated, Fine Steel Wire Armored,PVC Sheathed Power Cable
YJV42 Copper Conductor, XLPE Insulated,Thick Steel Wire Armored,PVC Sheathed Power Cable For laying in shaft, water underground and large diference of level, able to bear external mechanical pressure and moderate pulling force.
YJLV42 Al.Conductor, XLPE Insulated,Thick Steel Wire Armored,PVC Sheathed Power Cable
 
 
Technical data
 
Rated voltage: 0.6/1kV, 1.8/3kV, 6/10kV, 8.7/10kV, 8.7/15kV, 12/20kV, 18/30kV, 21/35kV, 26/35kV
Maximum Conductor Temperature: under normal (90°C), emergency (130°C) or short circuit no more than 5 s (250°C) conditions.
Min. Ambient Temp. 0°C, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D for single-core non-armoured cables
                                15 x cable O.D for single-core armoured cables
                                15 x cable O.D for multi-core non-armoured cables
                                12 x cable O.D for multi-core armoured cables
 